INGENIO: UPS 30 – 50 kVA 3/3

3/3 phase UPS 30-50 kVA

Three-phase output Uninterruptible Power Supplies for servers, network and telecom devices, safety and emergency systems, building automation, medical equipment.
 

  • Small size and high power density
  • Paralleled solutions up to 300 kVA
  • High autonomy times capability
  • Customization for harsh environment applications

 

Benefits:
  • Minimum amount of installation space: this series features extremely small dimensions and one of the lowest footprint in its range
  • Low running cost: high efficiency and ECO mode reduce overall power losses and thus energy costs
  • No electrical system oversizing: full IGBT technology providing smooth sinusoidal input current cuts all system oversizing costs
  • Easy commissioning and quick maintenance: removable power modules and simple handling for low installation and service times

 

Features:
  • High double conversion efficiency and ECO mode for low running costs and environmental impact
  • Transformer free design for light small size layout
  • Removable power modules architecture and built-in diagnostics for easy maintenance and very low MTTR
  • Hot connection/disconnection of parallel units for easy system resizing
  • Full IGBT technology and electronic PFC, ensuring 0.99 input PF and THDi<3% for maximum upstream sources compatibility
  • Wide range of configurations with internal batteries for low TCO compact solutions
  • High power battery charger, suiting long autonomy applications
  • Dual DSP plus microcontroller logics for top performance and reliability
  • CAN-bus based distributed parallel control ensuring high load sharing accuracy and no single point of failure
  • Comprehensive set of communication options for total remote monitoring of equipment operation
  • Fully compliance with all international product standards for maximum quality guarantee

INGENIO 30 to 50 kVA technical data

Rating (kVA) 30 40 50
Nominal power (kW) 27 36 45
UPS dimensions WxDxH (mm) 500x940x1500
UPS weight (kg) 140 150 190
UPS weight with int. battery (kg) 500 510 550
Battery configuration Internal or external, 360÷372 cells, VRLA (other options)
Max autonomy with int. battery 70% load (min) 24 16 12

Input

Connection type Hardwired 4w (separate bypass input available on request)
Nominal voltage 400 Vac 3-phase with neutral (rectifier)
380/400/415 Vac 3-phase with neutral (bypass)
Voltage tolerance -20%, +15% (rectifier) ±10% (bypass)
Frequency and range 50/60 Hz, 45÷65 Hz
Power factor 0.99
Current distortion (THDi) <3%

Output

Connection type Hardwired 4w
Nominal voltage 380/400/415 3-phase with neutral
Frequency 50/60 Hz
Voltage regulation ±1% static; dynamic: IEC/EN 62040-3 Class 1
Power factor up to 0.9, lagging or leading without power derating
Overload capability Inverter: 101÷125% for 10 min, 126÷150% for 30 s, >150% for 100 ms, bypass: 150% continuous, 1000% for 1 cycle
Efficiency (AC/AC)* Up to 98%
Classification as per IEC EN 62040-3 VFI-SS-111

*according to IEC/EN 62040-3

Connectivity and function extensions

Front panel Touch screen display
Remote communication Serial RS232 and USB; input terminal block for remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont.
Optional: input terminal block for diesel mode aux. cont., SNMP adapter (Ethernet), web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; UPS managing and server shutdown software
Optional function extensions Isolation transformer, external maintenance bypass, custom battery cabinets, wall-mounted battery fuse switch box, battery thermal probe, load-sync box

System

Protection degree IP 20
Colour RAL 9005
Installation layout Wall and side by side installation allowed; 50 cm clearance on one side with internal battery

Environmental

Operating temperature 0°C ÷ +40°C
Storage temperature -10°C ÷ +70°C
Altitude (AMSL) < 1000 m without power reduction, > 1000 with reduction of 0.5% per 100 m
Audible noise at 1m (dBA) <52

Standards and certifications

Quality assurance, environment,
health and safety
ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007
Safety IEC EN 62040-1
EMC IEC EN 62040-2
Environmental aspects IEC EN 62040-4
Test and performance IEC/EN 62040-3 VFI-SS-111
Protection degree IEC 60529
Marking CE