INGENIO: UPS 30 – 50 kVA 3/3
3/3 phase UPS 30-50 kVA
Three-phase output Uninterruptible Power Supplies for servers, network and telecom devices, safety and emergency systems, building automation, medical equipment.
- Small size and high power density
- Paralleled solutions up to 300 kVA
- High autonomy times capability
- Customization for harsh environment applications
Benefits:
- Minimum amount of installation space: this series features extremely small dimensions and one of the lowest footprint in its range
- Low running cost: high efficiency and ECO mode reduce overall power losses and thus energy costs
- No electrical system oversizing: full IGBT technology providing smooth sinusoidal input current cuts all system oversizing costs
- Easy commissioning and quick maintenance: removable power modules and simple handling for low installation and service times
Features:
- High double conversion efficiency and ECO mode for low running costs and environmental impact
- Transformer free design for light small size layout
- Removable power modules architecture and built-in diagnostics for easy maintenance and very low MTTR
- Hot connection/disconnection of parallel units for easy system resizing
- Full IGBT technology and electronic PFC, ensuring 0.99 input PF and THDi<3% for maximum upstream sources compatibility
- Wide range of configurations with internal batteries for low TCO compact solutions
- High power battery charger, suiting long autonomy applications
- Dual DSP plus microcontroller logics for top performance and reliability
- CAN-bus based distributed parallel control ensuring high load sharing accuracy and no single point of failure
- Comprehensive set of communication options for total remote monitoring of equipment operation
- Fully compliance with all international product standards for maximum quality guarantee
INGENIO 30 to 50 kVA technical data
Rating (kVA) | 30 | 40 | 50 |
Nominal power (kW) | 27 | 36 | 45 |
UPS dimensions WxDxH (mm) | 500x940x1500 | ||
UPS weight (kg) | 140 | 150 | 190 |
UPS weight with int. battery (kg) | 500 | 510 | 550 |
Battery configuration | Internal or external, 360÷372 cells, VRLA (other options) | ||
Max autonomy with int. battery 70% load (min) | 24 | 16 | 12 |
Input
Connection type | Hardwired 4w (separate bypass input available on request) |
Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
Voltage tolerance | -20%, +15% (rectifier) ±10% (bypass) |
Frequency and range | 50/60 Hz, 45÷65 Hz |
Power factor | 0.99 |
Current distortion (THDi) | <3% |
Output
Connection type | Hardwired 4w |
Nominal voltage | 380/400/415 3-phase with neutral |
Frequency | 50/60 Hz |
Voltage regulation | ±1% static; dynamic: IEC/EN 62040-3 Class 1 |
Power factor | up to 0.9, lagging or leading without power derating |
Overload capability | Inverter: 101÷125% for 10 min, 126÷150% for 30 s, >150% for 100 ms, bypass: 150% continuous, 1000% for 1 cycle |
Efficiency (AC/AC)* | Up to 98% |
Classification as per IEC EN 62040-3 | VFI-SS-111 |
*according to IEC/EN 62040-3
Connectivity and function extensions
Front panel | Touch screen display |
Remote communication | Serial RS232 and USB; input terminal block for remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont. Optional: input terminal block for diesel mode aux. cont., SNMP adapter (Ethernet), web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; UPS managing and server shutdown software |
Optional function extensions | Isolation transformer, external maintenance bypass, custom battery cabinets, wall-mounted battery fuse switch box, battery thermal probe, load-sync box |
System
Protection degree | IP 20 |
Colour | RAL 9005 |
Installation layout | Wall and side by side installation allowed; 50 cm clearance on one side with internal battery |
Environmental
Operating temperature | 0°C ÷ +40°C |
Storage temperature | -10°C ÷ +70°C |
Altitude (AMSL) | < 1000 m without power reduction, > 1000 with reduction of 0.5% per 100 m |
Audible noise at 1m (dBA) | <52 |
Standards and certifications
Quality assurance, environment, health and safety |
ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
Safety | IEC EN 62040-1 |
EMC | IEC EN 62040-2 |
Environmental aspects | IEC EN 62040-4 |
Test and performance | IEC/EN 62040-3 VFI-SS-111 |
Protection degree | IEC 60529 |
Marking | CE |