INGENIO PLUS: UPS 60 – 160 kVA 3/3

3/3 phase UPS 60-160 kVA

Low TCO, efficient and compact solution for supplying reliable uninterrupted quality power to all critical applications in networking and small to medium datacenter, health, finance, industrial processing, building and transportation markets and for TLC.

Featuring Green Conversion patented technology, INGENIO PLUS provides high efficiency even at light loads and ensures 100% battery expected life, thus ensuring low opex and capex savings.

Application:

  • Networking and telecommunication
  • Data server
  • Process automation
  • Medical equipment
  • Emergency and safety systems
  • Continuous cooling

 

Benefits:
  • Continuous savings with Green Conversion patented technology, providing high efficiency and UPS critical components’ life care
  • Clean mains and full compatibility with Genset operation due to its low input current distortion and soft start features
  • No costs related to electrical infrastructure oversizing and power factor correction thanks to its 0.99 input PF
  • Reduced commissioning and floor space related costs and lower environmental footprint with transformer free design and common battery management
  • Capital expenditure protection thanks to hot expandability and load based shutdown in parallel systems
  • High flexibility for all types of loads with full output power rating and different operating modes

 

Features:
  • Green Conversion technology, high efficiency even at light load and the lowest TCO in its category
  • Ultra High Efficiency mode, the ultimate innovation protecting high immunity grade applications, providing 99% efficiency and lowest operational expenditure
  • Full rated output power, ensuring optimal UPS sizing and utilization
  • Transformer free design for compact, light and sustainable systems
  • Full IGBT technology and electronic PFC, ensuring 0.99 input PF and THDi <3% for maximum upstream sources compatibility
  • Internal battery configurations up to 80 kVA for less floor space and maximum flexibility
  • Dynamic Charging Mode (DCM) for maximum versatility in long autonomy and low charging time applications
  • Intermittent battery charge, with adjustable cycle, providing capital expenditure protection and extreme efficiency savings
  • Common battery management for even more compact and cost saving UPS systems
  • Load based unit shutdown for highest efficiency in light loaded parallel systems
  • Comprehensive set of communication options for total remote monitoring of equipment operation

INGENIO PLUS 60 to 160 kVA technical data

Rating (kVA) 60 80 100 125 160
Nominal power (kW) 60 80 100 125 160
UPS dimensions WxDxH (mm) 560x940x1800
UPS weight (kg) 250 300 320 360 380
UPS weight with int. battery (kg) 800 850
Battery configuration Internal or external, 360÷372 cells,
VRLA (other options)
External 360÷372 cells, VRLA (other options)
Max autonomy with int. battery 70% load (min) 16 11

Input

Connection type Hardwired 4w (rectifier), 4w (bypass)
Nominal voltage 400 Vac 3-phase with neutral (rectifier)
380/400/415 Vac 3-phase with neutral (bypass)
Voltage tolerance -20%, +15% (rectifier) ±10% (bypass)
Frequency and range 50/60 Hz, 45÷65 Hz
Power factor >0.99
Current distortion (THDi) <3%

Output

Connection type Hardwired 4w
Nominal voltage 380/400/415 3-phase with neutral
Frequency 50/60 Hz
Voltage regulation ±1% static; dynamic: IEC/EN 62040-3 Class 1
Power factor up to 1, without power derating
Overload capability Inverter: 101÷125% for 10 min, 126÷150% for 30 s, >150% for 0.1 s;
bypass: 150% continuous, 1000% for 1 cycle
Efficiency (AC/AC)* Up to 99%
Classification as per IEC EN 62040-3 VFI-SS-111

*according to IEC/EN 62040-3

Connectivity and function extensions

Front panel Graphic display, mimic LED panel and keyboard, local EPO
Remote communication Included: serial RS232 and USB, backfeed protection monitoring contact.
Input terminal block (remote emergency power off, battery circuit breaker aux. cont.,
external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.);
Optional SNMP adapter (Ethernet), Web interface (Ethernet), from ModBus-RTU to PROFIBUS DP adapter;
SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software
Optional function extensions Isolation transformer; transformers/autotransformers for voltage adjustment;
external maintenance bypass; custom battery cabinets; wall-mounted battery fuse
battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems)

System

Protection degree IP 20
Colour RAL 9005
Installation layout Wall and side by side installation allowed, 80 cm clearance on one side only with internal battery
Accessibility Front access, side access (only with internal battery), bottom cable entry

Environmental

Operating temperature 0°C ÷ +40°C
Storage temperature -10°C ÷ +70°C
Altitude (AMSL) < 1000 m without power reduction, > 1000 with reduction of 0.5% per 100 m
Audible noise at 1m (dBA) <60

Standards and certifications

Quality assurance, environment,
health and safety
ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007
Safety IEC EN 62040-1
EMC IEC EN 62040-2
Environmental aspects IEC EN 62040-4
Test and performance IEC/EN 62040-3
Protection degree IEC 60529
Marking CE