E3001.e AC UPS 5-200 kVA 3ph / 3ph

3-Phase Input / 3-Phase Output on-line double conversion UPS

Industrial, heavy duty AC UPS with full galvanic insulation.
Designed to Supply critical AC loads with stabilized continuous supply, in the Oil & Gas, Petrochemical, Power & Utilities applications.
 

  • Built-in inverter transformer for DC/AC galvanic separation
  • Input Transformer for AC/DC galvanic separation and SCR rectifier for reliable operation in all mains condition
  • High personalization grade, thanks to the modular layout
  • 16 Bit microcontroller control, digital control panel with history of alarms, full set of communications options

 

Benefits:
  • The product firmware, can be fully customized as for the customer request, adding easily any features required. Borri has the capability to made any modification internally, reducing at the minimum the time and cost required.
  • The product layout, allow to the final user the possibility of an easy and fast maintenance. All the components are well disposed inside the unit, and the panels can be installed against the walls.
  • The product can be easily added to any existing project, thanks to the experience and know how of Borri engineering team. The customer will be supported from our technical department, along the entire cycle of the project.
  • The product include an advanced user interface, and powerful tools for troubleshooting and monitoring. All the basic and advanced operations, will be done using simply the user interface of front panel.

 

Features:
  • IGBT,PWM controlled inverter for high efficiency and low output THD
  • Standard configuration for cost-effective, short lead time solutions
  • Easy integration with external devices like Explosion Proof enclosure, Distribution Panels, Bypass Transformers, Voltage Regulators
  • Comprehensive set of communication ports, like RS232 / USB / RS485 available as standard, for total remote monitoring
  • Support vented/sealed lead acid batteries and vented/gas recombination NiCd batteries
  • High-Speed last generation microcontroller, for best-in-class performance and reliability
  • High personalization grade of the internal layout and user interface
  • Active parallel configuration via CANBUS connection, dynamic parallel mode and sync control available

E3001.e technical data

Rating (kVA) 5 10 15 20 30 40 50 60 80 100 120 160 200
Nominal power (kW) 4 8 12 16 24 32 40 48 64 80 96 128 160

Input

Input voltage 380/400/415 (optional 208/480) Vac 3-phase ±10%, 50/60 Hz ±10%
Input THDi 27% 6p, 12% 12p, 6% THD filter +12p
Bypass input voltage 200/208/220 or 380/400/415 (optional 480) Vac ±20%
(adjustable according to inverter output voltage)

Battery

DC voltage available DC bus voltages vary with requested output AC voltages and rating (see the table below)
Rating 5 10 15 20 30 40 50 60 80 100 120 160 200
Output voltage 200÷220 Vac 110 Vdc (90÷160 Vdc range)
220 Vdc (180÷300 Vdc range)
380÷415 Vac 110 Vdc (90÷160 Vdc range)
220 Vdc (180÷300 Vdc range)
220 Vdc (180÷300 Vdc range)
Operating battery voltage Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable
Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable
Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable

Output

Nominal voltage 200/208/220/380/400/415 (optional 480) Vac 3-phase
Frequency 50/60 Hz (selectable), ± 0.001 Hz free running, ±2 Hz synchronized with mains
Voltage regulation ±1% static; ±5% dynamic (80% load change), <40 ms recovery time
Overload capacity 125% for 10 min; 150% for 1 min; 200% for 100
Harmonic Distortion THDv <2% linear load; <5% non-linear load

System

Isolation Floating battery; input/output isolation available with additional bypass transformer
Dimensions WxD (mm) Height is 2100 mm, width and depth vary with input voltage and rating (see the table below)
Rating 5 10 15 20 30 40 50 60 80 100 120 160 200
Input voltage 110 Vdc 800 1400×800 1600×800 2000×800 2000×1000 2400×1000
220 Vdc 800 1200×800 1400×800*
1200×800**
1400×800 1600×800 2400×800*
1600×800**
2400×800 2000×800** 2000×1000** 2400×1000**
Maximum weight (kg) 460 520 620 670 750 850 950 1150 1250 1400 1520 1680 1970
Cooling Forced ventilation
Efficiency 88%
Colour RAL 7035
Protection degree (IEC 60529) IP20 (other options)

Environmental

Operating temperature -10 °C ÷ +40 °C
Storage temperature -20 °C ÷ +70 °C
Altitude <2000 m (derating according to EN 62040-3)
Audible noise at 1 meter (dBA) <65÷75
Options Associated battery cabinets and distribution panels; bypass isolation transformer and AC/AC voltage stabilizer;
12 pulse bridge; THD filters; built-in battery breaker; timed battery charging; external battery breakers in standard or Eex-d wall-mounted box; battery thermal probe; parallel redundant, hot-standby, load-sync;
AC and DC earth fault alarm; fan monitoring and alarm; redundant ventilation; additional RFI filters; top cable entry

User Interface

Front panel LCD display, LED mimic, keyboard. Customisable status and alarms LED set
Connectivity SPDT contact relay card, RS232 serial port
Optional: RS485 ModBus-RTU serial port, ModBus to PROFIBUS DP adapter, Ethernet SNMP/WEB
adapter, remote monitoring software, up to 2 additional SPDT contact relay cards

*400 Vac **208 Vac