B8033FXS: UPS 10 – 100 kVA 3/3
3/3 phase UPS 10-100 kVA
Three-phase output Uninterruptible Power Supplies for servers, network and telecom devices, safety and emergency systems, building automation, medical equipment.
- Small size and high power density
- Paralleled solutions up to 600 kVA
- High autonomy times capability
- Customization for harsh environment applications
Benefits:
- Minimum amount of installation space: this series features extremely small dimensions and one of the lowest footprint in its range
- Low running cost: high efficiency and ECO mode reduce overall power losses and thus energy costs
- No electrical system oversizing: full IGBT technology providing smooth sinusoidal input current cuts all system oversizing costs
- Easy commissioning and quick maintenance: removable power modules and simple handling for low installation and service times
Features:
- Online double conversion UPS, VFI-SS-111 classification as per IEC EN 62040-3
- ECO mode and transformer free design for reduced running costs and low environmental impact
- Removable power modules architecture, positioning wheels and built-in diagnostics for easy maintenance and extremely low MTTR
- Full IGBT technology and electronic PFC, ensuring 0.99 input PF and THDi<3% for maximum upstream sources compatibility
- Accurate battery management providing ripple current minimization charge current/voltage control as per batteries manufacturers’ specifications and automatic/manual battery test for maximum battery expected life preservation
- High power battery charger, giving long autonomy and low charging time
- Dual DSP plus microcontroller logics for top performance and reliability
- CAN-bus based distributed parallelcontrol ensuring high load sharing accuracy and no single point of failure in parallel systems
- Comprehensive set of communication options for total remote monitoring of equipment operation
- Fully compliance with all international product standards for maximum quality guarantee
B8033FXS technical data
Rating (kVA) | 10 | 15 | 20 | 30 | 40 | 50 | 60 | 80 | 100 |
Nominal power (kW) | 9 | 13.5 | 18 | 27 | 36 | 45 | 54 | 72 | 90 |
UPS Dimensions WxHxD (mm) | 450x1200x670 * | 460x1690x920 | |||||||
UPS weight (kg) | 100 | 110 | 110 | 140 | 140 | 170 | 170 | 328 | 333 |
UPS weight with internal battery (kg) | Min.175 Max. 285 |
Min.260 Max. 275 |
Min.260 Max. 275 |
350 | 350 | – | – | – | – |
External battery module dimensions WxHxD (mm) |
500x1200x670500x1200x670 | 560x1690x880 | |||||||
Battery configuration | Internal or external, 360÷372 cells, VRLA (other options) | External, 360÷372 cells, VRLA (other options) |
Input
Connection type | Hardwired 4w (separate bypass input available on request) |
Nominal voltage | 380/400/415 Vac 3-phase with neutral |
Voltage tolerance | -20%, +15% |
Frequency and range | 50/60 Hz (45÷65 Hz) |
Power factor | 0.99 |
Current distortion (THDi) | <3% |
Output
Connection type | Hardwired 4w | |
Nominal voltage | 380/400/415 Vac 3-phase with neutral | |
Frequency | 50/60 Hz | |
Voltage regulation | ±1% static; dynamic: IEC EN 62040-3 Class 1 | |
Power factor | up to 0.9, lagging or leading without power derating | |
Overload capacity | Inverter: 101÷125% for 10 min, 126÷150% for 30 s, >150% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
Inverter: 101÷125% for 10 min, 126÷150% for 1 min, 151÷199% for 10 s, 200% for 100 ms; bypass: 150% continuous, 1000% for 1 cycle |
Efficiency (AC/AC)** | up to 98% | |
Classification as per IEC EN 62040-3 |
VFI-SS-111 |
Connectivity and function extensions
Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
Remote communication | Serial RS232 and USB; terminal block for battery breaker auxiliary contact. Optional: input terminal block (remote emergency power off, battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.); SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
Optional function extension | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit |
System
Protection degree | IP 20 |
Colour | RAL 7016 (10-60 kVA) RAL 9005 (80-100 kVA) |
Installation layout | 10 cm wall-gap, side by side installation allowed |
Accessibility | Front and top access, bottom cable entry |
*dimensions of 30 and 40 kVA with internal battery: 450x1730x670 **according to IEC EN 62040-3
Other features
Environmental
Operating temperature range | 0 °C ÷ +40 °C |
Storage temperature range | -10 °C ÷ +70 °C |
Altitude | <1000 m |
Audible noise at 1m (dBA) | <62 |
Standards and certifications
Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, GOST, BS OHSAS 18001:2007 |
Safety | IEC EN 62040-1 |
EMC | IEC EN 62040-2 |
Test and performance | IEC EN 62040-3 (VFI-SS-111) |
Protection degree | IEC 60529 |
Marking | CE |