B9600FXS: UPS 400 – 800 kVA 3/3
3/3 phase UPS 400-800 kVA
Three-phase output Uninterruptible Power Supplies for heating, ventilation and air conditioning equipment, safety and emergency systems, process control devices and machine tooling, critical infrastructures, medical equipment, data center monolithic power protection.
- Rugged design and high reliability
- Paralleled solutions up to 4.8 MVA
- Optimised system configuration for ICT applications
- Customization for specific process applications
Benefits:
- Optimised installation space: accurate airflow design preventing positioning costraints provides free system layout design to fully take advantage of the available installation area
- Low running cost: high efficiency and ECO mode reduce overall power losses and thus energy costs
- No electrical system oversizing: full IGBT technology providing smooth sinusoidal input current cuts all system oversizing costs
- Minimum maintenance costs: full front accessibility to all components and high material quality extremely reduce servicing
Features:
- Online double conversion UPS, VFI-SS-111 classification as per IEC EN 62040-3
- High double conversion efficiency and ECO mode for low running costs and low environmental impact
- Built-in inverter transformer for DC-AC galvanic protection of industrial type loads
- Hot connection/disconnection of paralleled units for easy system resizing
- Full IGBT technology and electronic PFC, ensuring 0.99 input PF and THDi<3% for maximum upstream sources compatibility
- Accurate battery management providing ripple current minimization charge current/voltage control as per batteries manufacturers’ specifications and automatic/manual battery test for maximum battery expected life preservation
- Dynamic Charging Mode (DCM) for maximum versatility in long autonomy and low charging time applications
- Smart parallel management in load sharing or load synchronization of two UPS and load synchronization of two paralleled systems for optimum protection
- Power and redundant parallel configurations with distributed or centralised static bypass for high fault current management
- Dual DSP plus microcontroller logics for top performance and reliability
- CAN-bus based distributed parallel control ensuring high load sharing accuracy and no single point of failure in parallel systems
- Comprehensive set of communication options for total remote monitoring of equipment operation
- Fully compliance with all international product standards for maximum quality guarantee
B9600FXS technical data
Rating (kVA) | 400 | 500 | 600 | 800 |
Nominal power (kW) | 360 | 450 | 540 | 720 |
Dimensions WxHxD (mm) | 1990x1920x990 | 2440x2020x990 | 2440x2020x990 | 3640x1920x990 |
UPS weight (kg) | 1820 | 2220 | 2400 | 3600 |
Battery configuration | External, 300÷312 cells, VRLA (other options) |
Input
Connection type | Hardwired 3w (rectifier), 4w (bypass) |
Nominal voltage | 380/400/415 Vac 3-phase (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
Voltage tolerance | -20%, +15% |
Frequency and range | 50/60 Hz (45÷65 Hz) |
Power factor | 0.99 |
Current distortion (THDi) | <3% |
Output
Connection type | Hardwired 4w |
Nominal voltage | 380/400/415 Vac 3-phase with neutral |
Frequency | 50/60 Hz |
Voltage regulation | ±1% static; dynamic: IEC EN 62040-3 Class 1 |
Power factor | up to 0.9, lagging or leading without power derating |
Overload capacity | Inverter: 101÷125% for 10 min, 126÷150% for 1 min, 151÷199% for 10 s; bypass: 150% continuous, 1000% for 1 cycle |
Efficiency (AC/AC)* | up to 98% |
Classification as per IEC EN 62040-3 |
VFI-SS-111 |
Connectivity and function extensions
Front panel | Graphical LCD display, mimic with LED and keyboard |
Remote communication | Serial RS232 and USB; input terminal block for: remote emergency power off (REPO), battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.; optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet); ModBus-RTU (RS485); ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
Optional function extension | Isolation transformer; transformers/autotransformers for voltage adjustment; maintenance bypass in extended cabinet or wall-mounted box; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit for load sharing; load synch box; top cable entry |
System
Protection degree | IP 20 (other options) |
Colour | RAL 7016 (other options) |
Installation layout | Wall, back to back and side by side installation allowed |
Accessibility | Front and top access, bottom cable entry |
*certified by TÜV NORD according to IEC EN 62040-3
Other features
Environmental
Operating temperature range | 0 °C ÷ +40 °C |
Storage temperature range | -10 °C ÷ +70 °C |
Altitude | <1000 m |
Audible noise at 1m (dBA) | <62 |
Standards and certifications
Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, GOST, BS OHSAS 18001:2007 |
Safety | IEC EN 62040-1 |
EMC | IEC EN 62040-2 |
Test and performance | IEC EN 62040-3 (VFI-SS-111) |
Protection degree | IEC 60529 |
Marking | CE |